Combined optical and thermovelocimetric detector - The detector integrates an NFC transceiver - Configuration and visualization through APP - Graph of the last detected alarm - Dynamic control and sensitivity compensation - Universal base mounting TFBASE01N
SKU: TF-TFDA-STR2
Ekskl. moms
Combined optical and thermovelocimetric detector - The detector integrates an NFC transceiver - Configuration and visualization through APP - Graph of the last detected alarm - Dynamic control and sensitivity compensation - Universal base mounting TFBASE01N
Configurable combination detector, can be used with analog or conventional control panels. The detector composed of 2 separate and independent detection sections, an optical smoke detector and thermo-velocimetric detector of Category A1-58°, suffix R.
The detector integrates an NFC transceiver with which, by means of a smartphone and the Tecnofire ID App, it is possible to configure the device and display: the identification data, the alarm counter, the graph of the last detected alarm (optical detector only) and the data necessary to manage the detector revision service. Highest accuracy in temperature detection and analysis of the captured smoke. Dynamic control and compensation of the sensitivity of the optical camera, automatic management of the maintenance threshold. Programmable functions: 3 sensitivity levels, excludable pre-alarm signaling, excludable optical detection section, formula association and management criterion for TFBASE-SIREN or TFRIP-SMART. The functional states of the detector can be used as operands in the formulas managed by the control panel.
CSR® Management: programming, remote management and control. Double line isolator. Base mounting
universal TFBASE01.
EN 54-7:2018 - EN 54-5:2017 + A1:2018 - EN 54-17:2005.
Certificate of homologation: 0051-CPR-3133
- TECNOFIRE
- Configurable combined detector
- Can be used with analog addressable or conventional control panels
- Composed of 2 separate and independent sensing sections
| Combined optical and thermovelocimetric smoke detector configurable | TFDA-STR2 |
| Detector configuration | Addressable or Conventional |
| APP: | iPhone - Android (Tecnofire ID) |
| NFC protocol | Encrypted |
| Programming | Read / Write |
| Recorded data | Optical alarm graphic Alarm counter Detector ID Revision management |
| Interrogation LED | Excludable |
| Sensitivity | 3 levels |
| Prealarm | Excludable |
| Optical sensing section | Excludable |
| Thermovelocimetric detector | Category A1-58° R Suffix |
| Management criteria | Programmable |
| Address | Software |
| Communication protocol | FIRE-SPEED |
| Line separator | Double insulator |
| Nominal voltage | 24VDC |
| Operating voltage | 18V…30VDC |
| Absorption | 400µA @ 24V DC |
| Absorption in alarm | 5mA @ 24V DC |
| Snooze alarm output | 9,4V DC 3mA |
| Operating temperature | -10°C...+55°C |
| Relative humidity (non-condensing) | (without condensation) 10%...93% |
| Degree of protection IP22 | relative humidity (non-condensing) |
| Box | ABS |
| Dimensions | (D x H) 100 x 52mm |
| Weight 100g | |
| Standards | EN 54-5:2017 + A1:2018 EN 54-7:2018 EN 54-17:2005 |
| Approval certificate 0051-CPR-3133 | (D x H) 100 x 52mm |
| Year of CE marking | 23 |
| Benefit statement number | 053_TFDA-STR2 |
| Certification body | IMQ |
- Combined optical and thermovelocimetric detector with isolator